Sounder700ISMRed FI700WMSOUR – 355180

The loop sounder FI700/WM/SOUR is activated and supplied via the ADM loop with Labor Strauss/700 protocol. Depending on the parameter setup of the Fire Detection Control Panel Series BC216 and the sy- stem condition, the panel can activate one of three tones. If several sounders are actuated in parallel, they are synchronised by the control panel to generate a uniform warning tone

In the event of a short circuit, the integrated dual-isolator interrupts the loop. With that, the function of all ADM elements that do not lie within the loop segment which is affected by the short circuit, is maintained

The sounder is integrated in a red plastic housing and is designed for indoor wall mounting. The sounder base and a special tool for opening the housing are included with the sounder

Tone 1: alternating tone 650Hz for 250ms, 990Hz for 250ms

Tone 2: continuous tone 990Hz

(Tone 3: interrupted tone 990Hz (0.5s ON, 0.5s OFF

Low power consumption Adjustable sound level

Address can be set in the range 1 to 240 by means of Programming Unit FI700/PU

Optional AUTO-addressing when combined with a compatible fire detection control panel